Resumen en español · Traducción disponible

VigenteObligatoria

GB5135.9-2018

Automatic sprinkler system—Part 9:Early suppression fast response (ESFR) sprinklers

自动喷水灭火系统 第9部分:早期抑制快速响应(ESFR)喷头

GB 5135.9-2018 es una norma nacional china obligatoria vigente: Automatic sprinkler system—Part 9:Early suppression fast response (ESFR) sprinklers. Sector: Medio ambiente. Enfoque: Seguridad de productos. Entrada en vigor: 1 abr 2019.

La aplicabilidad depende del alcance del producto, la vía de certificación, los avisos de la autoridad competente y las reglas de transición. Solicite una traducción o verifique la fuente antes de usar esta ficha en una decisión de cumplimiento.

Resumen de cumplimiento

Este resumen está disponible por ahora solo en inglés.

Alcance y aplicabilidad

This standard applies to Early Suppression Fast Response (ESFR) sprinklers with nominal flow coefficients of K202 (pendent and upright), K242 (pendent and upright), K323 (pendent), and K363 (pendent). It is specifically designed for high-challenge fire hazards such as high-piled storage warehouses. This standard is mandatory for all manufacturers producing ESFR sprinklers for the Chinese market, and it explicitly excludes special application sprinklers.

Requisitos técnicos

The standard mandates comprehensive physical and thermal performance criteria for ESFR sprinklers. It specifies general design rules, such as prohibiting rubber seals at the water outlet and ensuring components cannot be easily adjusted. Manufacturers must ensure the frame and thermal sensing elements withstand specific mechanical loads and fatigue stresses without permanent deformation or failure. It defines strict parameters for flow coefficient (K-factor) tolerances and water distribution performance. The standard requires specific Actual Delivered Density (ADD) limits, ensuring sufficient water penetrates the fire plume to reach the burning surface. Additionally, it sets boundaries for static operating temperatures, response time index (RTI), and conductivity factor (C). The document also outlines rigorous environmental and corrosion resistance requirements. Sprinklers must survive extreme conditions including vibration, impact, freezing, and high temperatures. Components must resist stress corrosion from ammonia, magnesium chloride, sulfur dioxide, hydrogen sulfide, and salt spray without compromising their operational integrity. Finally, it establishes fire suppression performance criteria through full-scale fire testing. This includes evaluating the maximum allowable number of operating sprinklers, ceiling steel beam temperature limits, and restrictions on flame propagation across aisles, using standardized plastic cup and foam plastic commodities.

Métodos de ensayo

The standard details a comprehensive suite of evaluation procedures, including hydrostatic seal and strength tests to verify pressure integrity. It mandates dynamic thermal tests using a wind tunnel to calculate the Response Time Index (RTI) and conductivity factor (C). Manufacturers must also conduct full-scale fire suppression tests using standardized commodities to evaluate actual fire performance. Furthermore, environmental durability is verified through salt spray, stress corrosion, and impact testing procedures.

Preguntas frecuentes

What products are regulated under GB 5135.9-2018?

The standard regulates Early Suppression Fast Response (ESFR) sprinklers with specific nominal flow coefficients of K202 (pendent and upright), K242 (pendent and upright), K323 (pendent), and K363 (pendent). It explicitly excludes special application sprinklers.

Are there any significant updates from the previous version of GB 5135.9?

Yes, compared to the 2006 version, this update added requirements for magnesium chloride stress corrosion resistance, K323 pendent sprinkler ADD and fire suppression performance, deflector strength, and K242 pendent sprinkler momentum requirements. It also modified dynamic thermal and fire suppression test methods.

How does GB 5135.9-2018 differ from international ISO standards?

The standard specifies precise testing parameters such as nominal operating temperatures, RTI values, and specific ADD limits. While it shares the fundamental testing philosophy of international ESFR standards (like NFPA or ISO standards), manufacturers must strictly adhere to the localized Chinese test configurations, fuel types, and pressure parameters detailed in this document to achieve CCC certification.

The summary above provides a high-level overview of GB 5135.9-2018. To ensure complete compliance for your products entering the Chinese market, a precise and professional translation of the full technical specifications is essential. Purchase our high-quality English translation of GB 5135.9-2018 today to access all detailed parameters, tables, and testing procedures.

Indicaciones de aplicabilidad

Tipo
Producto
CCS
C83
ICS
13.220.10
Organismo competente
National Fire and Rescue Administration
Comité técnico
National Technical Committee on Fire Protection of Standardization Administration of China

Relaciones

Sustituye a:GB 5135.9-2006