Résumé en français · Traduction disponible

À venirObligatoire

GB16670-2025

Cabinet gas fire extinguishing equipment

柜式气体灭火装置

GB 16670-2025 est une norme nationale chinoise obligatoire à venir : Cabinet gas fire extinguishing equipment. Secteur : Machines. Thème principal : Sécurité des produits. Entrée en vigueur : 1 juil. 2026.

L’applicabilité dépend du périmètre du produit, de la voie de certification, des avis des autorités et des règles de transition. Demandez une traduction ou vérifiez la source avant d’utiliser cette fiche pour une décision de conformité.

Aperçu de conformité

Cet aperçu n’est actuellement disponible qu’en anglais.

Champ d’application

This standard applies to cabinet heptafluoropropane gas fire extinguishing equipment and cabinet carbon dioxide gas fire extinguishing equipment stored in high-pressure form. It is not applicable to cabinet carbon dioxide gas fire extinguishing equipment stored in low-pressure form. Manufacturers of fire protection systems for industrial and commercial facilities must ensure their products comply with these mandatory requirements.

Exigences techniques

The standard specifies comprehensive requirements for the composition, performance, and safety of cabinet gas fire extinguishing equipment. Key technical parameters include working temperature ranges, storage pressure, and maximum filling density. The equipment must support automatic, manual, and optionally mechanical emergency startup modes. Manufacturers must ensure the equipment features clear warning signs and reliable linkage performance. It also details requirements for critical components such as cylinder assemblies, container valves, safety relief devices, and low-leakage high-seal valves. Furthermore, the standard introduces new requirements for concentration distribution performance and a status monitoring and data application platform.

Méthodes d’essai

The standard outlines a rigorous testing protocol to verify compliance. Key evaluations include hydraulic strength tests, air tightness tests, and vibration tests to ensure structural integrity. Engineers must conduct concentration distribution tests to confirm the equipment can extinguish open flames within 30 seconds after discharge. Additional assessments cover corrosion resistance (salt spray, stress, sulfur dioxide), temperature cycling leakage, and impact resistance for accidental discharge protection devices. Performance tests for pressure displays, weighing devices, and signal feedback devices are also mandated.

Questions fréquentes

What products are regulated under GB 16670-2025?

GB 16670-2025 regulates cabinet heptafluoropropane gas fire extinguishing equipment and high-pressure stored cabinet carbon dioxide gas fire extinguishing equipment. It excludes low-pressure stored CO2 systems.

Are there any updates from the previous version of GB 16670?

Yes, compared to GB 16670-2006, this version adds requirements for warning signs, concentration distribution performance, and a status monitoring and data application platform. It also introduces new testing methods for accidental discharge protection devices and low-leakage high-seal valves.

Does GB 16670-2025 reference other standards?

Yes, it extensively references GB 25972-2024 for gas fire extinguishing systems and components, as well as GB 18614 for heptafluoropropane agents and GB 4396 for carbon dioxide agents.

The summary above provides a high-level overview of GB 16670-2025. To ensure complete compliance for your products entering the Chinese market, a precise and professional translation of the full technical specifications is essential. Purchase our high-quality English translation of GB 16670-2025 today to access all detailed parameters, tables, and testing procedures.

Indications d’applicabilité

Type
Produit
CCS
C84
ICS
13.220.10
Autorité compétente
National Fire and Rescue Administration
Comité technique
National Technical Committee on Fire Protection of Standardization Administration of China

Relations