Résumé en français · Traduction disponible
GB26875.1-2011
Remote-monitoring system of urban fire protection - Part 1: User information transmission device
城市消防远程监控系统 第1部分:用户信息传输装置
GB 26875.1-2011 est une norme nationale chinoise obligatoire en vigueur : Remote-monitoring system of urban fire protection - Part 1: User information transmission device. Secteur : Construction. Thème principal : Sécurité des produits. Entrée en vigueur : 1 mai 2012.
L’applicabilité dépend du périmètre du produit, de la voie de certification, des avis des autorités et des règles de transition. Demandez une traduction ou vérifiez la source avant d’utiliser cette fiche pour une décision de conformité.
Aperçu de conformité
Cet aperçu n’est actuellement disponible qu’en anglais.
Champ d’application
This standard applies to user information transmission devices used in urban fire remote-monitoring systems installed in general industrial and civil buildings. It is specifically designed for devices that transmit fire alarm and facility status information to a monitoring center. It does not cover the monitoring center software or network protocols themselves, which are addressed in other parts of the GB 26875 series.
Exigences techniques
This standard specifies the technical requirements for user information transmission devices used in urban fire remote-monitoring systems. The standard mandates that devices must be capable of receiving and transmitting fire alarm information and building fire facility status to a monitoring center within 10 seconds. Devices must prioritize fire alarm and manual alarm signals over other operational data. Key requirements include manual alarm functionality, self-check capabilities, and power supply redundancy with automatic switchover between main and backup power. The standard also defines strict electromagnetic compatibility (EMC) and environmental endurance criteria, ensuring reliable operation under electrical interference, temperature extremes, and mechanical vibration. Software must be stored in non-volatile memory and protected against unauthorized modifications. Compliance with these requirements is mandatory for market access.
Méthodes d’essai
The standard outlines a comprehensive testing protocol to verify compliance, including functional tests for alarm transmission, power supply switchover, and fault alarm mechanisms. It mandates insulation resistance and electrical strength tests to ensure safety. Environmental reliability is assessed through low temperature and damp heat tests, while mechanical robustness is verified via vibration and collision tests. Electromagnetic compatibility is evaluated using methods aligned with the GB/T 17626 series for immunity to electrostatic discharge, radiated electromagnetic fields, and electrical fast transients.
Questions fréquentes
What products are covered under GB 26875.1-2011?
It applies to user information transmission devices installed in general industrial and civil buildings as part of an urban fire remote-monitoring system. It does not apply to other system components like communication servers or management software.
Are the requirements in GB 26875.1-2011 mandatory?
Yes, Chapters 4 and 7 are mandatory, while the remaining chapters are recommended. Manufacturers must comply with the mandatory technical requirements and marking rules.
Does GB 26875.1-2011 reference international standards?
The standard references several national standards, including GB 50440 for technical specifications and the GB/T 17626 series for electromagnetic compatibility testing methods. It is primarily aligned with Chinese national practices for fire monitoring systems.
The summary above provides a high-level overview of GB 26875.1-2011. To ensure complete compliance for your products entering the Chinese market, a precise and professional translation of the full technical specifications is essential. Purchase our high-quality English translation of GB 26875.1-2011 today to access all detailed parameters, tables, and testing procedures.
Indications d’applicabilité
- Type
- Produit
- CCS
- C81
- ICS
- 13.220.20
- Autorité compétente
- National Fire and Rescue Administration
- Comité technique
- National Technical Committee on Fire Protection of Standardization Administration of China
Relations
Remplacée par:GB 26875.9-2026 (À venir)