CurrentMandatory

GB26859-2011

Safety code of electric power industry - Part of electric lines

电力安全工作规程 电力线路部分

GB 26859-2011 is a current mandatory Chinese national standard for Safety code of electric power industry - Part of electric lines. It appears in the Electronics compliance cluster with a product safety focus and has an implementation date of Jun 1, 2012.

Applicability depends on product scope, certification route, competent authority notices and transition rules. Requst for the translation or verify source before using this record in a compliance decision.

Compliance overview

Scope and applicability

This standard specifies the basic electrical safety requirements for power production units and personnel working in power production sites. It is applicable to operating electrical equipment and related sites of power generation enterprises with facilities of 66kV and above, transmission, substation, and distribution enterprises with facilities of 35kV and above, and power consumption units with facilities of 220kV and above. Other power enterprises and power consumption units may also refer to this standard for safety compliance.

Technical requirements

The standard outlines comprehensive safety protocols for electric power line operations, covering personnel qualifications, site conditions, and operational measures. It mandates specific safety organizational measures, including the use of various work tickets (e.g., First Kind Work Ticket, Second Kind Work Ticket), work permits, supervision, and work conclusion procedures to ensure a systematic approach to hazard prevention. Furthermore, it details safety technical measures that must be implemented before and during operations. These include strict procedures for power outages, voltage verification, installation of grounding lines and personal security lines, and the proper placement of warning signs and barriers. The standard also provides specific safety distance requirements between workers and live parts under various voltage levels. The standard extensively covers operational guidelines for line maintenance, work near live conductors, and specific tasks such as high-altitude operations, tower construction, and stringing. It also sets forth specialized requirements for live working and power cable work, emphasizing environmental safety, tool usage, and emergency protocols. Appendix E specifically regulates the testing items, cycles, and requirements for insulated safety tools.

Testing methods

The standard includes an appendix detailing the testing methods and cycles for insulated safety tools. Key tests involve the starting voltage test and power frequency withstand voltage test for capacitive voltage detectors and insulating rods. It also specifies DC resistance tests for portable grounding lines and personal security lines, as well as leakage current tests for insulating boots and gloves to ensure the integrity of personal protective equipment (PPE).

FAQs

What voltage levels of facilities are covered by GB 26859-2011?

It applies to power generation facilities of 66kV and above, transmission/substation/distribution facilities of 35kV and above, and power consumption facilities of 220kV and above.

Is GB 26859-2011 a mandatory standard?

Yes, with the exception of Chapter 5 and section 7.3.4 which are recommended, all other provisions of this standard are mandatory for the specified facilities.

What are the core technical safety measures required by this standard?

The core technical measures include power outages, voltage verification, installation of grounding and personal security lines, and the erection of warning signs and physical barriers.

The summary above provides a high-level overview of GB 26859-2011. To ensure complete compliance for your products and operations entering the Chinese market, a precise and professional translation of the full technical specifications is essential. Purchase our high-quality English translation of GB 26859-2011 today to access all detailed parameters, tables, and testing procedures.

Applicability hints

Type
Safety
CCS
K09
ICS
29.020
Competent department
National Energy Administration
Technical committee
National Energy Administration