UpcomingMandatory

GB26875.9-2026

Remote-monitoring system of urban fire protection—Part 9: User information transmission device

城市消防远程监控系统 第9部分:用户信息传输装置

GB 26875.9-2026 is an upcoming mandatory Chinese national standard for Remote-monitoring system of urban fire protection—Part 9: User information transmission device. It appears in the Construction compliance cluster with a product safety focus and has an implementation date of Mar 1, 2027.

Applicability depends on product scope, certification route, competent authority notices and transition rules. Requst for the translation or verify source before using this record in a compliance decision.

Compliance overview

Scope and applicability

This standard applies to the design, manufacturing, and inspection of user information transmission devices used in urban fire protection remote-monitoring systems installed in general industrial and civil buildings. It is mandatory for manufacturers producing transmission devices for the Chinese market. The standard categorizes these devices into general-purpose types (with local display and query functions) and gateway types (without local display). It does not apply to the monitoring center software or the fire alarm systems themselves, which are covered by other parts of the GB 26875 series.

Technical requirements

The standard specifies comprehensive technical requirements for transmission devices, focusing on appearance, main components, and operational functionality. Devices must feature clear indicator lights and displays, with specific requirements for sound pressure levels and visibility under certain lighting conditions. Manufacturers must ensure devices can receive and transmit fire facility status information within 10 seconds. The standard mandates features like manual alarm, self-inspection, breakpoint continuation, and time synchronization reception. Regarding electrical and power requirements, the standard outlines criteria for main and backup power supplies, including automatic conversion and backup battery capacity. Devices must withstand specified power parameter fluctuations and maintain insulation performance and electrical strength. Compliance with strict electromagnetic compatibility (EMC) performance is required to ensure stability under various interference conditions. Environmental durability is also a core requirement. The devices must endure climatic environmental tolerance tests, including low-temperature operation and constant damp heat, as well as mechanical environmental tolerance tests for vibration and impact. Additionally, the standard sets forth software requirements, mandating that programs be stored in non-volatile memory and protected against unauthorized modifications. Operation levels must be clearly defined and protected through identity verification.

Testing methods

The standard details rigorous testing methodologies to verify compliance. Key tests include the fire facility status information reception and transmission test, which measures response times and prioritization of fire alarms. Other critical evaluations involve power parameter fluctuation tests, insulation resistance tests, and electrical strength tests. Electromagnetic compatibility is assessed through various immunity tests, such as radio-frequency electromagnetic field radiation and electrostatic discharge tests, referencing standards like GB/T 17626.2. Environmental resilience is verified through low-temperature operation, constant damp heat, and vibration (sine) tests in accordance with GB/T 16838.

FAQs

What products are regulated under GB 26875.9-2026?

This standard regulates user information transmission devices used in urban fire protection remote-monitoring systems, specifically those installed in general industrial and civil buildings. It covers both general-purpose and gateway-type devices.

Are there any updates from the previous version of GB 26875.9-2026?

Yes, this standard replaces GB 26875.1-2011. Key updates include the addition of classification, appearance requirements, breakpoint continuation, time synchronization reception, and leakage current requirements, along with revised testing methods and inspection rules.

How does GB 26875.9-2026 relate to other standards?

It is Part 9 of the GB 26875 series on urban fire protection remote-monitoring systems. It references several other standards for testing, including GB/T 16838 for environmental tests and various parts of GB/T 17626 for electromagnetic compatibility tests.

The summary above provides a high-level overview of GB 26875.9-2026. To ensure complete compliance for your products entering the Chinese market, a precise and professional translation of the full technical specifications is essential. Purchase our high-quality English translation of GB 26875.9-2026 today to access all detailed parameters, tables, and testing procedures.

Applicability hints

Type
Product
CCS
C81
ICS
13.220.20
Competent department
National Fire and Rescue Administration
Technical committee
National Technical Committee on Fire Protection of Standardization Administration of China

Relationships

Replaces:GB 26875.1-2011 (Current)