CurrentMandatory

GB26860-2011

Safety code of electric power industry - Electric part of power plants and transformer substations

电力安全工作规程 发电厂和变电站电气部分

GB 26860-2011 is a current mandatory Chinese national standard for Safety code of electric power industry - Electric part of power plants and transformer substations. It appears in the Electronics compliance cluster with a product safety focus and has an implementation date of Jun 1, 2012.

Applicability depends on product scope, certification route, competent authority notices and transition rules. Requst for the translation or verify source before using this record in a compliance decision.

Compliance overview

Scope and applicability

This standard applies to the electrical equipment and related workplaces in power generation enterprises with facilities of 66kV and above, transmission, substation, and distribution enterprises with facilities of 35kV and above, and power consumption units with facilities of 220kV and above. It is mandatory for all relevant personnel and facilities operating within these voltage levels. Other power enterprises and consumers may refer to it as a guideline.

Technical requirements

GB 26860-2011 establishes the fundamental electrical safety requirements for personnel and workplaces in the electric power industry. It comprehensively outlines safety organizational measures, including the application of various work tickets (such as the first and second category work tickets), work permission, supervision, and termination procedures. Strict adherence to these administrative protocols is essential for operational compliance. The standard details safety technical measures that must be implemented before and during electrical work. This includes specific protocols for power outages, voltage verification, installation of grounding wires, and the proper placement of warning signs and barriers. It also covers general operational requirements for electrical equipment, emphasizing safe distances and operational sequences to prevent accidents. Furthermore, the standard provides specialized safety requirements for various high-risk scenarios, including live working, maintenance of generators and high-voltage motors, operations on SF6 electrical equipment, and work on secondary systems. It also addresses safety protocols for electrical testing and power cable operations, ensuring comprehensive risk management across different electrical tasks.

Testing methods

The standard includes a normative appendix detailing the testing items, cycles, and requirements for insulation safety tools. Key testing methods involve power frequency withstand voltage tests and DC resistance tests for equipment such as capacitive voltage detectors, portable short-circuit grounding wires, insulating rods, insulating boots, and insulating gloves. Regular testing according to these specified cycles is mandatory to ensure the integrity of safety equipment.

FAQs

What products or facilities are regulated under GB 26860-2011?

It regulates electrical equipment and workplaces in power plants and substations, specifically targeting facilities operating at 66kV and above for generation, 35kV and above for transmission and distribution, and 220kV and above for consumption units.

Is GB 26860-2011 a mandatory standard?

Yes, with the exception of Chapter 5 and clause 7.3.4 which are recommended, all other provisions of this standard are mandatory.

Does the standard specify requirements for safety equipment testing?

Yes, Appendix E is a normative appendix that specifies the testing projects, cycles, and requirements for various insulation safety tools, including withstand voltage tests for insulating rods and gloves.

The summary above provides a high-level overview of GB 26860-2011. To ensure complete compliance for your operations and facilities entering the Chinese market, a precise and professional translation of the full technical specifications is essential. Purchase our high-quality English translation of GB 26860-2011 today to access all detailed parameters, work ticket formats, and testing procedures.

Applicability hints

Type
Safety
CCS
K09
ICS
29.020
Competent department
National Energy Administration
Technical committee
National Energy Administration